Troubleshooting

Laser Outer Diameter Gauge

- LMD Series

Handling the Laser Outer Diameter Gauge

Mounting Orientation

There are no restrictions. However, if the glass faces downward after installation, it gets dirty more easily and needs thorough maintenance.

Impact from External Force

The precision rotary motor, lenses, mirrors, and other parts inside the detector are sensitive to external impact. Shocks such as dropping the unit can cause a failure.

Electrical Noise and Surges

Strong electrical noise from inverters, relays, solenoids, and other equipment can cause malfunctions.

Fully ground the mounting bases of the detector and display unit to a common ground. A floating ground can cause malfunctions and may even damage the equipment.

Ambient Temperature

Use the equipment at an ambient temperature of 40°C or below.

Above 40°C, electronic components deteriorate faster. The semiconductor laser in the detector in particular has a shorter service life at higher temperatures.

Water Droplets, Oil, and Smoke

Water (droplets), oil, or smoke on the detector can cause malfunctions or failures. Remove them thoroughly so that they do not splash onto the detector.

Daily Inspection

As routine maintenance, clean the glass window of the detector with a wiper moistened with alcohol or a similar cleaner.

Also check the accuracy with a pin gauge or similar tool at least every 6 to 12 months.

Other Precautions for Use

Connecting or disconnecting the cables while the power is on may cause a failure. Always turn the power off before connecting or disconnecting cables.

Do not route the connection cables together with power lines. Electrical noise can cause malfunctions.

Maintenance

The maintenance a laser outer diameter gauge needs is cleaning the detector glass.

Install the gauge where the glass is unlikely to get dirty. If steam or smoke reaches the installation site, blow it away or extract it.

Protection Against Water

Never install the gauge where water droplets splash. If there is a water trough in front of the detector, drain the product well so that no wet product passes through the measurement area.

Even if it is hard to see, the product may be wet or carrying steam when you look closely. We recommend touching the product with a tissue or similar to check.

Precautions When Cleaning the Glass

Wipe off dirt with a soft cloth, avoiding tissues where possible. Alcohol or a similar cleaner makes cleaning more effective.

Dirt or oil may remain in the corners of the glass, so wipe the entire glass surface clean.

If the glass is not cleaned properly, the display unit may show erratic values, the HOLD lamp may light up, or an error may occur and stop measurement.

If the problem persists after cleaning the glass, the unit needs to be repaired by us.

Troubleshooting Basics

For problems caused by dirt or scratches on the glass, masking the affected area with vinyl tape may help.

If you have a working detector and display unit set in addition to the set with the problem, you can narrow down whether the problem lies in the detector, the display unit, or the cable.

In the illustration on the left below, A is the set with the problem and B is the working set.

  1. Replace the detector with working detector B, or connect cable B to the connector of detector A (upper right in the figure below).
    • If this solves the problem on side A, the problem is in detector A.
  2. If the problem persists, replace the display unit with working display unit B, or connect working cable B to the connector of display unit A (lower right in the figure below).
    • If this solves the problem on side A, the problem is in display unit A.
    • If the problem still persists, the problem is in cable A.
How to locate a fault by swapping the detector, cable, and display unit

Likewise, if only one side of a two-axis measurement system has a problem and the other side works, you can use the method shown above to narrow down the cause.

Even after you identify the faulty part, if a repair by us is needed, please send the detector and display unit together as a pair where possible.

Troubleshooting by Symptom

The HOLD LED Lights Up Frequently

On the LDM-110/210/130/1000/1300 series the HOLD lamp lights up; on the LDM-100 series the position lamps (the eight LEDs below the numeric display) light up.

In this case, the laser element and scanning motor are often working normally, and the problem is mainly a disturbed detection signal from the detector.

On the LDM-110/1000/210 series, if this happens frequently and continuously, it eventually becomes an "E-14" error.

Holds are caused by the edge monitoring function, so first take the measures described in "Maintenance" and "Troubleshooting Basics" above. Problems that are not resolved by cleaning the glass generally require repair by us.

If you use a two-axis detector such as the LDM-304H-XY or LDM-305H-XY and this error occurs when measuring glossy products such as metal rods or wire wrapped in aluminum tape, laser light reflected from the glossy surface may be entering the receiver of the other axis and causing interference.

Diagram showing the angle at which the laser light strikes the product

In this case, install the detector at a slight angle so that the laser light does not strike the product surface perpendicularly.

Note, however, that the larger the angle, the larger the displayed diameter compared with the actual diameter. The size of the error can be calculated geometrically from the angle α.

Error = (1/cos α − 1) × 100 [%]

For example, when α = 7°, the error is 0.75%.

The Upper and Lower Limit Alarms Do Not Work at All

The most common cause is setting the upper and lower limits as absolute values.

To save you from resetting them every time the product changes, our laser outer diameter gauges set the upper and lower limits as deviations from the center value set with REF PRESET.

For example, to output a lower limit alarm at 1.9 mm or less and an upper limit alarm at 2.11 mm or more for a 2 mm product, set REF PRESET: 02.000, HIGH LIMIT: 0.110, and LOW LIMIT: 0.100.

If you instead set absolute values of HIGH LIMIT: 2.110 and LOW LIMIT: 1.900, the alarms will not work between 0.1 mm (PRESET 2 − LOW LIMIT 1.9) and 4.11 mm (PRESET 2 + HIGH LIMIT 2.11).

Example settings for REF PRESET, HIGH LIMIT, and LOW LIMIT

If this is not the cause, the display unit is most likely faulty. Please request a repair.

Stopped Working After a Board Was Moved to a Different Slot (LDM-1000/1000EX)

Check the following items.

  • Is the board ID switch set to F?
  • Do any installed boards share the same ID switch setting?
  • Is the board fully inserted into the slot?

The third item is a surprisingly common cause. After inserting a board, press it firmly into place by hand once more.

"E-00" Error (LDM-100 Series)

"E-00" is an error code specific to the LDM-100 series. It does not appear on the display units of the LDM-110 series or later.

It indicates that the detector is not outputting a detection signal. The most likely causes are a laser element breakdown or a scanning motor failure.

Other possible causes include insufficient cleaning of the detector glass, or a detector originally shipped as a pair with an LDM-110 being connected.

Some early LDM-100 models do not support this code in their program, so they show a "0000" error instead of "E-00" and can no longer measure.

"E-12" Error

The "E-12" error indicates that the detector is not outputting a detection signal. The most likely causes are a laser element breakdown or a scanning motor failure.

During an "E-12" error, the LED indicating that the laser is on may blink. This is because the display unit fires the laser once every 3 seconds to check whether it has returned to normal; the display unit blinks it on purpose to prevent hazards from laser light while the error is active.

On the LDM-210, "E-12" may also appear if the detector scan rate is not set correctly.

With CPU version 2.11 or later, the CPU version appears on the measurement display at power-on and the scan rate is shown on the green indicator LED. Please check these values.

If you use a version earlier than 2.11, check parameter No. 12. If it ends in 0, the scan rate is 2000 scans; if it ends in 1, it is 400 scans.

"E-14" Error

When the "E-14" error appears, the laser element and scanning motor are often working normally, but the detection signal from the detector is disturbed.

Before "E-14" occurs, the measured value often goes into hold frequently. Holds are caused by the edge monitoring function, so first take the measures described in "Maintenance" and "Troubleshooting Basics" above.

On the LDM-210, "E-12" may also appear if the detector scan rate is not set correctly.

With CPU version 2.11 or later, the CPU version appears on the measurement display at power-on and the scan rate is shown on the green indicator LED. Please check these values.

If you use a version earlier than 2.11, check parameter No. 12. If it ends in 0, the scan rate is 2000 scans; if it ends in 1, it is 400 scans.

"E-41" Error

"E-41" is an RS-232C error.

This error is almost always caused by mismatched communication settings (baud rate, parity, etc.) between devices, most often a baud rate mismatch.

On some models, settings do not take effect until the power is turned off and on again. If changing the baud rate switch does not change the setting, try restarting the power.

Outer Diameter Control Unit

- DAC Series

Troubleshooting by Symptom

The Extruder or Take-Up Speed Changes the Moment AUTO Is Engaged

Before AUTO is engaged, the signal from the speed potentiometer to the motor passes straight through the outer diameter control unit. The moment AUTO is engaged, it no longer passes straight through.

The most common cause of unstable motor speed at this point is induced voltage caused by long wiring runs.

Keep the potentiometer – outer diameter control unit – motor wiring as short as possible. Twisting each signal line with its paired 0 V line also helps.

If you use shielded cable, simply changing how the shield is handled, such as disconnecting it from ground, may improve the situation.

Diameter Fluctuations Persist Even with Control Engaged

Some diameter fluctuations can be controlled by the outer diameter control unit and some cannot.

In general, fluctuations with a period shorter than the time the product takes to travel from the extruder outlet to the outer diameter gauge cannot be controlled. These are often caused by uneven extruder rotation or slipping take-up pulleys.

Control by the outer diameter control unit works well on long-period fluctuations caused by changes in material mixing, temperature changes, clogged screens in the extrusion head, and similar factors.

Control may also fail because of how the outer diameter control unit is set up. Please check the settings again according to the instruction manual.

Control Stopped Working After the Outer Diameter Gauge Was Replaced

When the outer diameter gauge connected to the DAC+88 outer diameter control unit is replaced, control often fails because communication is lost due to a different communication speed.

If control fails even though the replacement display unit is the same model, check the setting switches on the back of the display unit that was connected before.

If you no longer know which display unit was connected, configure the settings according to the table below.

Display unit modelHow to check the LDM display unit settingDAC+88 communication setting
LDM-110Check that "BAUD" on the back is set to "4".Check that it is set to 1200 bps.
LDM-210Check that Select No. 1 is set to "3".Check that it is set to 1200 bps.
LDM-110EXSet DIP switch SW3 positions 7 and 8 on the back both to up.Check that it is set to 300 bps.
LDM-1000EXCheck that "BAUD" on the back is set to "4".Check that it is set to 1200 bps.

To set or check the DAC+88 communication speed, turn the power switch off, then turn it on while holding down the "MODE" button.

When you have finished, turn the power switch off, wait a few seconds, and turn it on again to apply the settings.

Slow Start-Up at Low Speed with Automatic Start-Up

During start-up, the automatic start-up unit pauses the ramp-up (holding the current line speed) unless the diameter is reasonably close to the set value, and repeats control until the diameter improves.

After the motor speed is fine-tuned based on the laser outer diameter gauge reading, you have to wait until the wire leaving the extruder passes the gauge detector to see how the diameter actually changed.

At low line speeds, it therefore takes time for a motor speed adjustment to show up as a change in diameter, so start-up at low speed is slow when the diameter is off.

You can address this problem as follows.

  • The best solution is to place the outer diameter gauge detector as close to the extruder outlet as possible, provided you can deal with steam and heat.
  • Improving the linearity of the extruder and take-up motors is also necessary. Ideally, the line should produce the same diameter at low speed when run at the same extrusion-to-take-up ratio as at high speed.

You can also tune the automatic start-up unit's parameters little by little, but this takes time and skill, and even after tuning, conditions may change with the outside air temperature or the state of the resin inside the extruder.

Automatic Start-Up Does Not Enter AUTO

Possible causes include the following.

  • Poor RS-232C connection, or a baud rate mismatch with the outer diameter gauge
  • No product in the measurement area of the outer diameter gauge (the gauge shows 0000)
  • The extrusion ON input (terminal 6) or take-up ON input (terminal 7) on the rear terminal block is OFF
  • The AUTO switch is faulty

Outer Diameter Irregularity Detector

- TM Series

Troubleshooting by Symptom

Both the Lump and Neck Lamps Stay Lit and the Unit Stops Working

This can happen on outer diameter irregularity detectors that use a white tungsten lamp as the light source, and is caused by a burnt-out lamp. (Most current models use an LED light source with a virtually unlimited service life.)

Replace the lamp following the procedure in the instruction manual. A spare lamp is stored inside the unit.

When opening the cover of the unit, be careful to open the correct side. Opening the wrong side will require readjustment by us.

False Alarms Without Any Lumps

Check the following possible causes. The smaller the lumps you want to detect, the more demanding the conditions become.

  • Is the glass dirty?
  • Is there moisture on the product?
  • Are water droplets, debris, dust, or other particles splashing or floating in the measurement area?
  • Is strong light such as sunlight falling on the unit? (Ordinary indoor fluorescent lighting is not a problem.)
  • Is the mounting area of the outer diameter irregularity detector vibrating?
  • Does the product jump significantly at the moment of the false alarm?

If you have the calibration gauge unit (option), try calibrating according to the instruction manual.

Counting Event Printer

- AD Series

Troubleshooting by Symptom

Nothing Prints After the Paper Was Replaced

Try turning the paper over.

The printer in the counting event printer uses thermal paper, so nothing prints if the paper roll is loaded with the wrong side facing out.

We have also seen malfunctions caused by using printer paper other than genuine paper.

Always use genuine printer paper.

Counts Are Incorrect

Possible causes include the following.

  • Miscounting due to noise

    In this case, single-phase pulse input tends to overcount, and A/B-phase pulse input tends to undercount. If there is a spark tester nearby, try moving it further away.

  • One pulse encoder is also connected in parallel to other equipment

    Adding a diode to each device connected in parallel may help.

  • The voltage level is not appropriate (when the pulse encoder uses voltage input)

    Check that the voltage level is appropriate. Use a 12 V DC level.

Joint / Break Detector

- ID Series

Troubleshooting by Symptom

Alarms Are Output Where There Is No Joint

Check the following possible causes.

  • Is the mounting area of the joint detection sensor vibrating?
  • Does the product jump significantly at the moment of the false alarm?
  • Is there a spark tester nearby?

Have a question?
Our team is ready to help.

Contact

Tel. +81-42-645-8920

Hours: 9:00–17:30 JST, Monday–Friday (excluding Japanese public holidays)

General Inquiries

Contact

Contact us about products, quotations, or documentation.

Contact Us Contact Us

Request a Quote

Quotation

Tell us about your application, and we will prepare a quotation.

Request a Quote

Brochures & Manuals

Download

Find the information you need to select and evaluate our products.

Download